KEMPER Hygiene System
|KHS CoolFlow
KHS CoolFlow cold water cooler
Item number 6100100100 Dimensions including packaging
€11,043.26 / Pcs
Nicht verfügbar
Tender text
KEMPER KHS CoolFlow cold water cooler,
figure 610 01 001, as flow-through
drinking water cooler for cooling
drinking water with integrated
circulation pump, for cooling and
distributing the cold water as far as
the tapping point outlet in the drinking
water installation, adjustment range of
PWC temperature 15 °C to 25 °C,
consisting of PWM-controlled circulation
pump with gunmetal housing and
integrated check valve, consisting of
PWM-controlled operating fluid pump,
with diffusion-tight insulation fitted
at the factory, pre-assembled, space
requirements less than 1 m², wetted
metal parts made from
dezincification-free and
corrosion-resistant gunmetal, resistant
to aggressive water, stainless steel and
drinking water-approved plastics, easy
operation with integrated commissioning
wizard, low-noise operation,
installation on the ground, incl.
drinking water-side maintenance
cut-offs, built-in operating fluid
buffer tank, allows efficient operation
of the cold water generator, connection
to cold water generator hydraulically
separated, integration of all cold water
generators possible, recharging request
through potential-free contact, compact
design, plate heat exchanger made of
stainless steel grade 1.4401/1.4404,
electronic control unit for high control
quality during operation, incl. Pt1000
measuring element, factory pre-assembled
electrical connection of actuators and
sensors to the control unit, plastic
parts with KTW and W 270 approval,
according to accepted materials list
from German environmental agency,
ÜA-Reg.-Nr. R-15.2.3-21-17048,
WIEN-ZERT, pressure stage PN 10 drinking
water side and PN 6 equipment side, min.
ambient temperature 0 °C, max. ambient
temperature 50 °C, max. cooling capacity
6.4 kW, power supply 230 V AC,
electrical power input 185.5 W,
note: maintenance and commissioning of
the plant on request, replaces version
610 01 000
max. head of cold water circulation pump: 10 m max. flow rate of cold water circulation pump: 2 m³/h
max. head of cold water circulation pump: 10 m max. flow rate of cold water circulation pump: 2 m³/h
Documents
Links
File type