Safety valves
|RPZ backflow preventer
PROTECT RPZ backflow preventer, type BA, union thread, DN 25
Item number 3600G02500 Dimensions including packaging 220 x 238 x 76 mm; 2.31 kg
€936.41 / Pcs
Tender text
KEMPER PROTECT RPZ backflow preventer,
type BA, union thread, figure 360 0G, to
protect drinking water against backflow
of fluids up to and including category 4
according DIN EN 1717 / DIN 1988-100,
wetted metal parts made from
dezincification-free and
corrosion-resistant gunmetal, resistant
against aggressive water, with stainless
steel mesh at inlet, integrated
differential pressure controlled and
low-maintenance protection cartridge
including CV, with controllable reduced
pressure zone, male union thread, with
three assembled valves, drain connection
of plastic and gunmetal according to DIN
EN 1717, inlet and outlet with check
cartridge, free from dead spots, for
horizontal installation, DVGW approval,
ÖVGW approval, SVGW approval up to DN
40, KIWA approval, BELGAQUA approval, VA
approval, according to UBA KTW BWGL,
according to UBA BWGL Metals, up to DN
20 sound protection class 1 up to DN 20
acc. DIN EN ISO 3822 (DN 25 & DN 32
Cl. 2), DIN EN 12729 (DN 50 with flow
values according to DVGW W 570)/EN 1717,
ÜA-Reg.-Nr. R-15.2.3-21-17048,
WIEN-ZERT, pressure rating PN 10, max.
operating temperature 60 GradC,
short-term peak temperature 65 GradC,
note: maintenance requirements in
accordance with DIN EN 806-5 must be
complied with
Technical data
Features
Type of fitting Tube separator
Housing style Durchgang
Housing material Rotguss
Nominal width 25 DN
Max. operating temperature 60 °C
Noise control class Sound protection class 1, DIN 4109
Connections
Inlet G 1 1/4
Outlet G 1 1/4
Waste water connection STECK-NIPP-DN 50
Performance curve
Performance curve is loading...
Documents
Technical documents
File type
CAD / BIM
File type
Safety Data Sheet for Hazardous Substances
File type
Other
File type
Accessories(12)
Spare parts

2 Spare parts
J71053600000200
test valve for RPZ backflow preventer PROTECT
3660000200
replacement cartridge for RPZ backflow preventer BA PROTECT and FK-4 RPZ backflow preventer outlet, for DN 25-32