LP Muli-Pro DDP 2.3 400V/50Hz
Item number 0175.13.25 Dimensions including packaging 1500 x 780 x 1550 mm; 420 kg
€16,073.98 / Pcs
Tender text
ACO Muli-Pro 2.3 lifting unit for
sewage containing faeces, for
free-standing installation
with sewer wheel
consisting of:
2 x collection tanks made of
polyethylene
each with inspection openings LW 250 mm
with overflow or underflow DN 150
with connecting sleeve made of
polyethylene
with drain plug and 3 x connection
for hand diaphragm pump R 1 1/2"
1 set of fixing screws with
washers and dowels for
buoyancy-proof anchoring
Tank dimensions: each 1500 x 780 x 1035
mm (LxWxH)
Total tank volume: 1040 liters
Useful tank volume:
with inlet height 600 mm = 480 liters
with feed height 750 mm = 610 liters
with inlet height 800 mm or from above =
660 liters
Inlet line connection:
2 x inlet DN 150, inlet height 600 mm
2 x inlet DN 150, inlet height 750 mm
2 x inlet DN 150, inlet height 800 mm
2 x inlet DN 100 from above, inlet
height 1015 mm
2 x inlet DN 200/150 from above, inlet
height 1015 mm
suitable for plastic or SML pipe
Connection pressure line:
2 special backflow preventers DN 80
with drain screw
with Y-pipe with special fastening-
for connection of pressure line DN 100
(outer pipe diameter 108
- 114.3 mm)
connection of ventilation pipe:
2 connecting pieces DN 100
suitable for plastic or SML pipe
2 pump units consisting of:
three-phase motor, floodable
Power: P1= 3,87 kW, P2= 3,0 kW
voltage 400 V, 50 Hz.
Speed: 1450 rpm.
protection class IP 68
with 1 shaft seal and
1 mechanical seal
with channel wheel
70 mm grain passage
incl. pneumatic level control:
pitot tube for ON-OFF ALARM 1
with pneumatic control line
and miniature compressor "air bubbling
(for protection against floating
media e.g. greasy waste water)
Control unit Multi Control
- Protection class IP 54
- Ready to plug in, with 1.5 m cable and
CEE plug (16 A)
with
integrated phase inverter
- Plastic housing for wall mounting,
dimensions 260 x 260 x
145 mm (WxHxD)
- potential-free collective fault and
operation signal
- mains-independent alarm and battery
(85dBA, 5-6h)
- numeric display with status indication
and -
digital potentiometer (rotary knob)
- digital potentiometer for setting pump
1 and 2
ON and OFF, switch-on delay after power
failure,
high water alarm, motor current
limitation, forced
switch-over and
forced switching on of the pumps
- Level measurement and sensor
monitoring
- Rotary field control
- H-0-A button
- Display of service intervals
- Operating hours counter and display of
switch-on pulses
- ammeter
- simple error memory (last error)
- automatic switch-over in case of pump
malfunction
- control preset and multilingual
- With 230V connection for air bubbling
power supply
The control box is connected to the
lifting unit by 10 m
pneumatic control line