KHS Flow-Splitter unit
- dynamic, for flush mounted installation, passage DN 20, outlets DN 20, valve DN 15
Commercial data
| Article number | 6500022000 |
| Price (non-binding sales price) (RSP) | 582.89 / Pcs |
| Main commodity group | KEMPER Hygiene System |
| Goods group | KHS Venturi Flow-Splitter dynamic |
Text of invitation to tender
KEMPER KHS Flow-Splitter unit
- dynamic, for flush mounted
installation, figure 650 00, prevents
stagnation in ring pipe installations
through forced flow during downstream
withdrawals, can be used in cold
drinking water (PWC) and hot drinking
water (PWH), KHS Flow-Splitter
- dynamic, according to the Venturi
principle, including dynamic cartridge,
flow and return branch for connection of
outlets / plumbing units, wetted metal
parts made from dezincification-free and
corrosion-resistant gunmetal, resistant
against aggressive water, KHS
Flow-Splitter pass with female thread,
plumbing unit feed pipe with female
thread, plumbing unit return pipe with
female thread, maintenance free, free
from dead spots, including quarter turn
stop valves, female threaded, for
flush-mounted installation, figure 585
00, maintenance-free EPDM spindle seal,
plastic shaft can be shortened,
removable inner top part TOP-ENTRY, with
EPDM gasket body and gunmetal ball,
incl. insulation shell made of
closed-cell foamed polyethylene,
valve(s) with DVGW approval, SVGW
approval, WRAS approval, according to
DVGW worksheet W 570, according to UBA
BWGL Metals, up to DN 32 soundproofing
certification according to DIN EN ISO
3822 Class 1, insulation shell building
material class B1 according to DIN 4102,
DIN EN 13828, ÜA-Reg.-Nr.
R-15.2.3-21-17048, WIEN-ZERT, max.
installation depth 110 mm, pressure
rating PN 16, max. operating temperature
90 GradC, note: for use in combination
with DN 25 handle set
Technical data
| Type of fitting | Ring line fitting |
| Width (mm) | 188 |
| Housing style | Durchgang |
| Housing material | Rotguss |
| Height (mm) | 137 |
| Weight (kg) | 2.02 |
| Max. operating temperature (°C) | 90 |
| Nominal width (DN) | 20 |
| Noise control class | Sound protection class 1, DIN 4109 |
| Depth (mm) | 248 |
Connections
| Input passage | Rp 3/4 |
| Output passage | Rp 3/4 |
| Outgoing ring | Rp 1/2 |
| Access ring | Rp 1/2 |
Characteristic line
Documents
CAD
Accessories
| Image | Description | |||
|---|---|---|---|---|
| handle for flush-mounted valves, for DN 25-32 | ![]() | 2 | ||
REACH statement
Building technology valves and systems
Flow Diagram Flow-Splitter
Installation and operating instructions KHS Venturi flow divider
Link to the website
Revit-Families COBie-Standard